RETA3092 Power Grid Measurement Module

Grid Transformer Interface Functional features ● For three-phase grid voltage measurement ● For three-phase grid current measurement ● Rail-mounted installation ● Easy to connect ● RS485 communication

Category:

RETA3092 Grid Transformer Interface Functional Features ● Used for three-phase grid voltage measurement ● Used for three-phase grid current measurement ● Rail-mounted installation ● Easy to connect ● RS485 communication Product Introduction The RETA3092 integrated power monitoring module has outstanding performance and more functions with a 32-bit ARM processor as the core; it uses 6-channel 16-bit A/D with 4K data rate synchronous AC sampling, digital filtering and calibration, and reasonable data processing algorithms to ensure data reliability and accuracy; voltage input, current input, and electric energy pulse output are all isolated from each other to ensure product reliability. The three-meter method can measure more than 40 three-phase electrical parameters of three-phase three-wire/four-wire AC circuits with high precision: voltage, current, active/reactive/apparent power, power factor, frequency, active/reactive energy, zero-sequence current, voltage imbalance, etc. The AC sampling technology is used to realize the four-quadrant power measurement of the receiving/feeding line, and has high-precision measurement of positive/reverse active energy and inductive/capacitive reactive energy. For more product information, please refer to the following related parameters. Technical Parameters

Related Features
Minimum
typical
maximum
unit
Power supply(DC)
18
24
36
V
Power consumption
3
W
Input voltage (AC phase voltage)
100
400
V
Voltage overload capability
600
V
Voltage input load
0.1
0.4
VA
Input Impedance
1
Current range
1
5
A
Current overload capability
10
A
Current input load
0.1
VA
Input frequency
45
50
60
Hz
Dielectric strength
100
Data Update
0.04
0.4
Second
Service life
50000
Hour
Operating temperature
-20
60
Scroll to Top